FX2N-16CCL-M CC-Link System Master Block
System Configuration 3
3-4
3.3.2
Scan time of PLC and connection of two or more master blocks
1) Measured scan time
-
Configuration:
[FX
2N
Series PLC main unit]+[FX
2N
-16CCL-M]+[7 remote I/O st[8 remote device
stations]
-
Number of link device points: 110 words
The scan time in the configuration above is 125 ms.
2) Handling when two or more master blocks are connected
Remote I/O stations can be connected only to the first master block.
To the second and later master blocks, only remote device stations (up to 8 stations) can be
connected.
-
Configuration:
[FX
2N
Series PLC main unit]
+[FX
2N
-16CCL-M (first module)]+[7 remote I/O st[8 remote device stations]
+[FX
2N
-16CCL-M (second module)]+[8 remote device stations]
-
Number of link device points: 206 words
The scan time in the configuration above is 233 ms.
3) Caution
If the total scan time in the PLC exceeds 200 ms, a watchdog timer error occurs. In this
case, change the value of the special data register D8000 in the PLC to prolong the
watchdog timer time.
Summary of Contents for FX2N-16CCL-M
Page 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Page 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Page 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Page 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Page 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Page 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Page 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Page 193: ......