FX2N-16CCL-M CC-Link System Master Block
System Configuration 3
3-8
3.5
System Equipment List
The table below shows the list of equipment constructing the CC-Link for the FX Series PLC.
Table 3.3:
Product name
Model name
Description
Number of
occupied
stations
Station
type
Master block
FX
2N
-16CCL-M
Master block for the FX
1N
/FX
2N
/FX
3U
/FX
2NC
Series
⎯
Master
station
FX Series PLC
connection
block
FX
2N
-32CCL
Interface block for connection of the FX
0N
/FX
1N
/FX
2N
/
FX
3U
/FX
2NC
Series
One station occupies 32 input points and 32 output
points.
However, 16 points of the last station is used as the
system area.
One station occupies 4 RWw and 4 RWr.
1 to 4
Remote
device
station
Remote I/O
module
AJ65BTB1-16D
1-line, 16-point DC input module (sink/source shared)
24V DC, 7 mA, 16 points/common
1
Remote
I/O
station
AJ65BTB2-16D
2-line, 16-point DC input module (sink/source shared)
24V DC, 7 mA, 16 points/common
AJ65BTC1-32D
1-line, 32-point DC input module (sink/source shared)
24V DC, 7 mA, 32 points/common
AJ65BTB1-16T
1-line, 16-point transistor output module (sink)
12/24V DC, 0.5 A/point, 4 A/common, 8 points/
common
AJ65BTB2-16T
2-line, 16-point transistor output module (sink)
12/24V DC, 0.5 A/point, 4 A/common, 8 points/
common
AJ65BTC1-32T
1-line, 32-point transistor output module (sink)
12/24V DC, 0.1 A/point, 2 A/common, 32 points/
common
AJ65BTB2-16R
2-line, 16-point contact output module
24V DC/240V AC, 2 A/point, 8 A/common, 8 points/
common
AJ65BTB1-16DT
I/O module
Input: 1-line, 8 DC input points (sink)
24V DC, 7 mA, 8 points/common
Output: 1-line, 8 transistor output points (sink)
12/24V DC, 0.5 A/point, 8 points/common
AJ65BTB2-16DT
I/O module
Input: 2-line, 8 DC input points (sink)
24V DC, 7 mA, 8 points/common
Output: 2-line, 8 transistor output points (sink)
12/24V DC, 0.5 A/point, 4 A/common, 8 points/
common
AJ65BTB2-16DR
I/O module
Input: 2-line, 8 DC input points (sink/source shared)
24V DC, 7 mA, 8 points/common
Output: 2-line, 8 contact output points
24V DC/240V AC, 2 A/point, 8 A/common, 8
points/common
Summary of Contents for FX2N-16CCL-M
Page 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Page 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Page 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Page 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Page 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Page 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Page 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Page 193: ......