'15 • HM-T-246
Code No.
Contents of display
Data display range
Minimum unit
Remarks
C60
CWFV opening
0
,
1
(0
;
Close, 1
;
Open)
―
Order of 100
:
CWFV5
Order of 10
:
CWFV6
Order of 1
:
Spare
C61
"Pressure switch
External input"
0
,
1
(
0
;
Open circuit
)
1
;
Short circuit
―
Order of 100
:
63H1-1
Order of 10
:
63H1-2
Order of 1
:
CNS1
C62
External input
0
,
1
(
0
;
Open circuit
)
1
;
Short circuit
―
Order of 100
:
CNS2
Order of 10
:
CNS3
Order of 1
:
CNG1
C63
External input
External output
0
,
1
(
0
;
Open circuit
)
1
;
Short circuit
―
Order of 100
:
CNG2
Order of 10
:
Operation output (CnH)
Order of 1
:
Error output (CnY)
C64
External output
0
,
1
(
0
;
Open circuit
)
1
;
Short circuit
―
Order of 100
:
External output (CNZ1)
Order of 10
:
External output (CNZ2)
Order of 1
:
Spare
C65
Relay output (Heater)
0
,
1
(
0
;
Open circuit
)
1
;
Short circuit
―
Order of 100
:
CH1
Order of 10
:
CH2
Order of 1
:
DH
C66
Relay output (Heater)
0
,
1
(
0
;
Open circuit
)
1
;
Short circuit
―
Order of 100
:
H1
Order of 10
:
H2
Order of 1
:
Spare
C67
Relay output (Cooling fan for control)
0
,
1
(
0
;
Open circuit
)
1
;
Short circuit
―
Order of 100
:
Coolig fan1
,
2
Order of 10
:
Ventilating fan
Order of 1
:
AC water pump
C68
Relay output (52X-1
,
2)
0
,
1
(
0
;
Open circuit
)
1
;
Short circuit
―
Order of 100
:
52X1-1
,
2
Order of 10
:
52X2-1
,
2
Order of 1
:
Spare
C69
Relay output (Solenoid valve)
0
,
1
(
0
;
Open circuit
)
1
;
Short circuit
―
Order of 100
:
SV-inj1
Order of 10
:
SV-inj2
Order of 1
:
SVHG1
C70
Relay output (Solenoid valve)
0
,
1
(
0
;
Open circuit
)
1
;
Short circuit
―
Order of 100
:
SVHG2
Order of 10
:
SV-oil1
Order of 1
:
SV-oil2
C71
Number of connected unit
1
‐
4
1unit
C72
Capacity of connected unit
0
‐
999
1kW
C73
Accumulated compressor operating time (CM1)
0
‐
655
100h
C74
Accumulated compressor operating time (CM2)
0
‐
655
100h
C75
Accumulated water pump operating time
0
‐
655
100h
C76
Accumulated compressor operating time from the
maintenance last time (CM1)
0
‐
655
100h
C77
Accumulated compressor operating time from the
maintenance last time (CM2)
0
‐
655
100h
C78
Accumulated water pump operating time from the
maintenance last time
0
‐
655
100h
C79
Operation mode
0
‐
10
―
See next page
C80
Target temperature to top up
0
‐
99
1
℃
C81
Target hot water temperature
0
‐
99
1
℃
C82
Target hot water amount
0
‐
99
1
℃
C83
Rate of effective demand
0
‐
100
1%
C84
Hot water amount
0
‐
127
1%
C85
Spare
―
―
<Control status>
C86
Control status
0
‐
127
1
C87
Protection control status
0
‐
127
1
C88
Compressor stop factor
0
‐
127
1
C89
Compressor stop factor lapsed time
0
‐
255
1
C90
Protection control factor1
0
‐
127
1
C91
Protection control factor2
0
‐
127
1
C92
Protection control factor3
0
‐
127
1
C93
Compressor anomaly detection factor1
0
‐
127
1
C94
Compressor anomaly detection factor2
0
‐
127
1
C95
Compressor anomaly detection factor3
0
‐
127
1
<Others>
C96
Data reset
C97
Program
・
sub-version
0
‐
991
―
C98
Program
・
POL-version
0.00
‐
9.99
0.01
C99
Auto feed display
―
―
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...