'15 • HM-T-246
E
E
Communication error between CP U of control P CBs
-time
. Applicable Model
. Troubleshooting
All models
Diagnosis
Countermeasure
Are the
wiring harnesses and
cables passing above
the CPU?
Is the
J-pin inserted to JPX2?
And is JP11
opened?
Does E89 recur?
After inserting
the J-pin to JPX2 and
opening the JP11,
does E89 recur?
NO
YES
YES
YES
NO
NO
NO
YES
After disconnect the J-pin from JPX2 and
short the JP11, rewrite the software
program of IC1 and IC2 to the latest
version.
Or replace the ROM to the latest version
one
CP U may be malfunctioned
Rearrange to keep
wiring away from the
circumference of CP U
IC is in software rewriting
mode.
Software program version
before rewritten was
unmatched.
Control P CB anomaly
Replace control P CB
. E rror detection method
When the communication
between CP Us is interrupted for
a certain period of time
. Condition of error displayed
If it occurs 4 times within
15 minutes
. P resumable cause
・Noise
・Mixing of software
versions
・Control PCB anomaly
N ote:
Error code
Remote control:
7-segment display:
LED
Green
Red
Heat pump
water heater
Keep
flashing
Content
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...