'15 • HM-T-246
Error code
Remote control:
7-segment display:
LED
Green
Red
Heat pump
water heater
Keep
flashing
Content
E
E
E mergency stop
-time
. Applicable model
. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
NO
YES
Is the
setting of emergency stop
by remote control
valid?
Does the
contact signal input to
CnT contact on
the control PCB?
Save the Mente PC data of 30
minutes before stopping
・
Check the operation
status and record it.
・
Check it occurs soon
after power ON or during
operation or during
stopping.
Replace control P CB
Replace control P CB
Check the cause for
occurring emergency stop
(It is better to have the
data of 0 minutes before
stopping for checking)
. E rror detection method
When the contact signal input
is input to CnT contact on the
control P CB of heat pump water
heater.
. Condition of error displayed
Same as above
. P resumable cause
・
Occurrence of emergency stop
factor
N ote: The heat pump water heater detected the emergency stop signal sends the command to make [All stop].