'15 • HM-T-246
Error code
Remote control:
7-segment display:
LED
Green
Red
Heat pump
water heater
Keep
flashing
Content
E
E -
Compressor anomaly by loss of synchronism
-time
. Applicable Model
. Troubleshooting
All models
Diagnosis
Countermeasure
Is this
the first time to start up within
1 hour after the power
ON?
Are there any
maintenance history to replace
inverter PCB?
Save the Mente PC data of 30
minutes before stopping
Check the data 30 minutes
before stopping
Compressor lock may cause.
Replace compressor
YES
NO
NO
YES
・
Check the operation
status and record it.
There is a possibility that
the liquid refrigerant is
migrated in the compressor.
Wait for about one hour
with keeping the power
source and then restart
operation.
(In order to evaporate the
liquid refrigerant migrated
in the compressor by power
source to the crankcase
heater.)
There is a possibility to
be done wrong setting of
model selection switch
Check the setting of dip
switch
. E rror detection method
When E is displayed on the
-segment LE D display
. Condition of error displayed
If this anomaly is established
times within minutes
. P resumable cause
・
Insufficient communication
hours before start operation.
(Start operation without power
source to the crankcase heater
in advance)
・
Compressor anomaly
N ote: If the same error does not reappear, continue to get data with Mente P C.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...