'15 • HM-T-246
. Applicable model
. Troubleshooting
All models
Diagnosis
Countermeasure
Before
starting operation, is the power
to the heat pump water heater
turned ON?
NO
YES
Reset the power source and restart operation
Is the
refrigerant amount adequate?
(If recharging refrigerant after rectification,
check whether the specified
refrigerant amount
was charged.)
NO
YES
NO
Is there
any leak of refrigerant?
Is balancing pressure higher or lower
than the pressure of saturated
temperature?*
YES
NO
Does
low pressure become
altered after starting
operation?
Does the
opening of EEVH1,
H2 change?
NO
Is the
connection of low pressure
sensor connector
OK?
NO
* In case of 31°C or lower
YES
NO
Is the EEV coil OK?
(Check continuity)
YES
YES
YES
The refrigerant may
be accumulated in the
accumulator.
After supplying power for
more than hours, restart
operation
P urge refrigerant and
recharge refrigerant
properly.
Refrigerant is leaking.
Specify the leak point and
after rectifying the leak
point, recharge refrigerant
properly
Correct the connection
Check the low pressure
sensor If it has a problem,
replace the sensor
Check connection
of connectors and
characteristics of sensors of
Th-R, -R, -R and -R
Replace E E V coil
Clogging of strainer or
anomaly of the E E V body
may cause.
Check them.
If it has a problem, replace
it.
. E rror detection method
Detection of anomalously low
pressure
• LP
<
.0MP a is detected for 0
seconds continuously
• LP
<
0.00MP a is detected for
seconds continuously
. Condition of error displayed
If error signal is detected
times within 0 minutes
. P resumable cause
• Leak of refrigerant
• E E V anomaly
N ote:
Error code
Remote control:
7-segment display:
LED
Green
Red
Heat pump
water heater
Keep
flashing
1-time
flash
Content
E
E -
Low pressure anomaly
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...