'15 • HM-T-246
Calculation of mechanical ventilation capacity
Installation of leak detector
[Note]
Monitor the concentration with an alarm type CO
densitometer.
Limit is lower than
1.5 m because leaked
CO
2
accumulates at
the bottom.
Necessary room space: 287 m
3
or larger
Necessary
floor area:
191 m
2
or more
Hot water
supply pipe
Water supply
pipe
CO
2
heat pump water heater
In the room
Exhaust opening
As low as possible
Air suction opening a)
Air
inlet
b)
Leaked
CO
2
Floor
surface
1.5 m or
lower
Air outlet
Lower than
0.3 m from
floor surface
[Caution]
When necessary
space in the room and
necessary floor area
are not available, a
mechanical ventilating
equipment must be
installed.
Opening for ventilation
must be positioned as
low as possible.
Ventilation:
31 m
3
/min or more
Hot water
supply pipe
Water
supply
pipe
CO
2
heat pump
water heater
In the room
Exhaust
opening
As low as
possible
Air suction opening a)
Air
inlet
b)
Floor surface
Air outlet
Lower than
0.3 m from
floor surface
Room temperature
… 25˚C or lower
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...