'15 • HM-T-246
. Applicable model
. Troubleshooting
All models
Diagnosis
Countermeasure
• Check the operation status and
record it.
Replace control P CB
Replace inverter P CB
Check the cause of F blown.
Check wiring mistake and short
circuit of AC00V line.
E specially check wiring mistake of
option parts CWFV and V .
After checking, replace fuse F.
Restart operation under the
operating conditions of 0 minutes
before error occurred as possible
as you can.
Wait and see
(If possible, collect the operation
data continuously)
High pressure sensor anomaly is
suspected.
After restarting operation, check
the high pressure sensor itself.
(If the high pressure sensor has
anomaly, replace it)
Check the disruption of feed
water.
Secure a supply of feed water.
Clear the clog
[Check items]
Gas cooler, Strainer,
Lack of water,
Clogging of gas cooler
Connect the connector
securely.
Rectify the disconnection
of H wire.
. E rror detection method
When the communication
between inverter P CB and
control P CB of heat pump water
heater is not established.
. Condition of error displayed
Same as above
. P resumable cause
• Disconnection of signal
wiring harness
• Control P CB anomaly
• Inverter P CB anomaly
• Anonaly of inrush current
suppression resistance
N ote:
If the same error does not reappear, continue to get data with Mente P C.
Error code
Remote control:
7-segment display:
LED
Green
Red
Heat pump
water heater
Keep
flashing
1-time
flash
Content
E
E -
Communication error
between inverter P CB and control P CB
High pressure anomaly (H- activated)
Go to next page
YES
YES
YES
Is the LED 1
on the inverter PCB
flashing ?
Does E45 recur ?
Is the LED 2
on the control PCB
flashing?
Reset the power source and restart
Is the LED 1
on the inverter PCB
flashing ?
Is the fuse F2 blown?
NO
Reset the power source and restart
Save the data 30 minutes
before stopping into the
Mente PC
NO
NO
NO
Does
63H1 activate at the
pressure 14MPa or
higher ?
Does
the high pressure
sensor (PSH1) show
14MPa?
Is the feed water pressure
100kPa or higher?
Was air purge done?
Does water stoppage
occur?
Is the
feed water OK?
Does the refrigerant
circuit get clogged?
Is
there loose
connection of 63H1at
the connector on the
PCB or disconnection
of 63H1wire ?
YES
NO
YES
YES
YES
YES
NO
NO
NO
YES
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...