'15 • HM-T-246
(3)-9 Detection of temperature or pressure sensors disconnection
() Starting condition
If one of following conditions is established;
①
Outdoor air temperature sensor, Heat exchanger temperature sensors, Intermediate receiver inlet temperature sensor, Suction
pipe temperature sensor, Gas cooler water temperature sensor
(a) The disconnection of sensor is detected for seconds continuously within 0 seconds after the power turns ON .
(b) The disconnection of sensor is detected for seconds continuously within minutes to minutes 0 seconds after the
compressor turns ON .
②
Low pressure sensor, High pressure sensor, Intermediate pressure sensor
(a) The disconnection of sensor is detected for seconds continuously within minutes to minutes 0 seconds after the com-
pressor turns ON .
③
Discharge pipe temperature sensor, Under-dome temperature sensor
(a) The disconnection of sensor is detected for seconds continuously within 0 minutes to 0 minutes 0 seconds after the
compressor turns ON .
④
P ower transistor temperature sensor
(a) The disconnection of sensor is detected for seconds continuously within 0 minutes to 0 minutes 0 seconds after the
compressor turns ON and it is detected at the outdoor air temperature
≧
0
℃
.
() Control conditions
If the judgment of either one of sensor disconnection is detected times within 0 minutes, it becomes error stop mode.
(3)-10 Outdoor fan motor anomaly
If one of following conditions is established, compressor is stopped.
(a) Under the outdoor fan control mode, the outdoor fan speed
≦
00min
-
is detected for 0 seconds continuously
(b) Under the fan control mode and the outdoor fan speed command
≦
speed, if the outdoor fan anomaly signal is detected
for 0 seconds continuously or if the compressor is stopped times within 0 minutes by the outdoor fan motor
anomaly, [E ] is displayed on the remote control and it becomes error stop mode.
(3)-11 Feed water inlet temperature anomaly
If feed water inlet temperature exceeds usage range, it makes the heat pump water heater stopped.
This control is for emergency avoidance against the transitional temperature increase.
() Starting condition
If [(a) and (b)] and [(c) or (d)] of following conditions are established.
(a) Compressor is ON
(b) N ot in defrost operation
(c) Following high water inlet temperature condition is established
[High water inlet temperature condition]
Feed water inlet temperature
>
℃
is detected for sec or more. (Upper limit)
Or at outdoor air temperature
≧
0
℃
, feed water inlet temperature
>
℃
is detected for sec or more.
(d) Following water inlet temperature change conditions is established
When 0degC or more temperature difference t of feed water inlet temperature (Tho-W) is detected for sec con-
tinuously.
() Control content
(a) Stop compressor and after minutes delay, restart compressor if ending condition is established.
(b) During establishing [High water inlet temperature condition], water pump is operated intermittently in case of connecting un-
vented cylinder.
(c) Other functional components comply with the behavior at compressor stopping.
() E nding condition
[High water inlet temperature condition]
Feed water inlet temperature
<
0
℃
.
Or at outdoor air temperature
≧
0
℃
, feed water inlet temperature
<
℃
.
[Water inlet temperature change condition , ]
When the starting condition is not established.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...