'15 • HM-T-246
* Check several times to prove any poor connection
[Sensor temperature-resistance characteristics]
Under-dome temperature sensor (Tho-C)
Temperature (° C)
Error code
Remote control:
7-segment display:
LED
Green
Red
Heat pump
water heater
Keep
flashing
Content
E
E -
Under-dome temperature sensor (Tho-C) anomaly
-time
. Applicable Model
. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
Is the
connector of the
anomalous sensor
connected
properly?
Are
the characteristics
of sensor OK?
*1
NO
Save the Mente PC data of 30
minutes before stopping
YES
・
Check the operation
status and record it.
・
Check it occurs soon
after power ON or during
operation or during
stopping.
・
Check sensing value
・
Compare the temperature
shown in menteP C data
to the acutal temperature
measured with
thermometer.
Insert the connector
securely
Replace under-dome
temperature sensor
(Tho-C)
Replace the control P CB of
heat pump water heater
. E rror detection method
Detection of anomalously low
temperature (resistance) of
temperature sensor. (Tho-C)
. Condition of error displayed
If the sensor detects -0° C or
lower temperature for seconds
continuously
. P resumable cause
・
Broken sensor harness or
the internal wire of sensing
section(Check the molded
section as well)
・
Disconnection of sensor
harness connection
(connector)
・
Control P CB anomaly
N ote:
00
0
0
0
0
0
0
0
0
0
0
-0
0
0
0
0
0
00
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...