'15 • HM-T-246
. Troubleshooting
Diagnosis
Countermeasure
Is there
DC10V or higher voltage on
the connecting terminal of
remote control?
YES
No display on the remote
control after the power is
supplied
After disconnecting
the remote control, can
DC10V or higher voltage be
detected on the
R/C wiring?
NO
NO
NO
YES
Is the
connecting wire between
the remote control and the
heat pump water heater connected
properly?
NO
YES
Is there
DC15V or higher
voltage between X and Y
terminals of heat
pump water heater?
NO
Is the
voltage between
①
and
②
of CN18V on the
control PCB
DC18V?
YES
NO
YES
Connecting wire disconnection
. E rror detection method
Condition of error displayed
• Blown fuse
• Disconnection of wire
between P CBs
• P ower P CB anomaly
• Disconnection of remote
control wire
• Heat pump unit control P CB
anomaly
Error code
Remote control:
LED
Green
Red
Heat pump
water heater
Stay off
Stay off
Content
on the remote control
AMP Air Conditioning
www.ampair.co.uk | [email protected]