'15 • HM-T-246
3.6 Guideline for indoor installation of CO
2
heat pump water heater
CO
concentration of CO
generates drain water.
Points for indoor installation
• P rovide emergency measures against leakage of CO
gas.
equipment.
• Drain water can be disposed safely.
(1) Emergency measures for refrigerant leakage
Measures to secure safety is necessary against an accidental leak of CO
it is assumed that the unit is
installed in a machine room
on the assumption that people will not
stay for a long period of time in the exposed environment.
[Calculation of RCL value for CO
2
]
concentration under the
×
Calculation of minimum necessary room volume
[Note]
E ven if total refrigerant charged in CO
the CO
[Necessary minimum room space for each CO
2
heat pump water heater]
Total refrigerant of CO
From total refrigerant of CO
.
Minimum room space
or larger to install the CO
heat pump water heater.
Since CO
is heavier than air and likely to concentrate at lower places
people.
×