'15 • HM-T-246
4.10 How to reset the accumulated water pump and compressor operating time
【
Timing to be displayed about periodical check 1, 2 & oPE-1
~
3,11
~
13
】
・
Q-ton announce the maintenance code and periodic check by the cumulative operating time of the water pump and
compressor. This announcement to the user can remind the maintenance check.
・
The table shows the timing of maintenance code and periodic check. And also, it shows how to reset the cumulative
operating time after periodic check
7-segment display of
accumulated operation time
(*1)
Maintenance code
Display of remote control
(
*2
)
How to reset
oPE Code
Timing to be displayed Display content Timing to be displayed
Water pump
C78
(Accumulated water pump
operating time from last
periodical check)
oPE-11(M11)
5,000h
Periodical
check 1
20,000h
1. Set the 7-segment to C78.
2. SW3-7 OFF
3. SW3-8 ON
oPE-12(M12)
10,000h
oPE-13(M13)
20,000h
Compressor
C76
(Accumulated compressor
operating time from last
periodical check(CM1))
oPE-1(M1)
5,000h
Periodical
check 2
30,000h
1. Set the 7-segment to C76.
2. SW3-7 OFF
3. SW3-8 ON
oPE-2(M2)
10,000h
oPE-3(M3)
30,000h
N ote
)
*
:
00h units
*
:
This function can be invalid by using SW- to ON
(
from Main ROMver..0
)
【
How to reset accumulated time of water pump and compressor after replacement
】
・
Accumulated time of water pump and compressor is counted. This info will be useful when servicing.
・
If it is replaced, make sure to reset its accumulated time for future service.
7-segment display of
accumulated operation time
(*1)
How to reset
Water pump
C75
(Accumulated water pump
operating time)
Set the 7-segment to C75.
Reset operation time by pressing the SW7 for 3 seconds.
Compressor
C73
(Accumulated compressor
operating time(CM1))
Set the 7-segment to C73.
Reset operation time by pressing the SW7 for 3 seconds.
Reference
C70
Relay output (Solenoid valve)
0
,
1
(
0
;
Open circuit
)
1
;
Short circuit
―
Order of 100
:
SVHG2
Order of 10
:
SV-oil1
Order of 1
:
SV-oil2
C71
Number of connected unit
1
〜
4
1unit
C72
Capacity of connected unit
0
〜
999
1kW
C73
Accumulated compressor operating time (CM1)
0
〜
655
100h
C74
Accumulated compressor operating time (CM2)
0
〜
655
100h
C75
Accumulated water pump operating time
0
〜
655
100h
C76
Accumulated compressor operating time from the
maintenance last time (CM1)
0
〜
655
100h
C77
Accumulated compressor operating time from the
maintenance last time (CM2)
0
〜
655
100h
C78
Accumulated water pump operating time from the
maintenance last time
0
〜
655
100h
C79
Operation mode
0
〜
10
―
See next page
C80
Target temperature. to top up
0
〜
99
1
℃
C81
Target hot water temperature.
0
〜
99
1
℃
C82
Target hot water amount
0
〜
99
1
℃
C83
Rate of effective demand
0
〜
100
1%
N ote
)
*
:
00h units
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...