'15 • HM-T-246
. Applicable model
. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
primary side of power source voltage
between phases
OK?
NO
YES
Save the Mente PC data of 30 minutes
before stopping
Reset the power source and restart
YES
NO
Is E32 displayed?
• Check the operation status
and record it.
• Check it occurs soon
after power ON or during
operation or during
stopping.
(When asking the customer
much easier to explain the
situation with these data.
Ask the customer to make
Check it under the operating
conditions 0 minutes
before error occurred as
possible as you can.
Replace control P CB
Check operation without
. E rror detection method
Check the power source voltage
of inlet side of control P CB.
(Check only L-phase)
. Condition of error displayed
If the power voltage between
L and L phases or L and L
phases becomes 0V .
. P resumable cause
• P ower source voltage failure
on primary side.
• Control P CB anomaly
N ote:
Error code
Remote control:
7-segment display:
LED
Green
Red
Heat pump
water heater
Keep
flashing
1-time
flash
Content
E
E
Open phase of power line
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...