'15 • HM-T-246
N o display
N o display
It can operate but no hot water comes out ()
Stay
OFF
. Applicable Model
. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
flow amount of water
circuit within the
range?
Is it
available to change
setting?
Is enough
hot water amount in the
cylinder secured after the operation
to fill up in the night
time?
YES
Check whether hot water comes out
Check availability to operate heat pump water heater
and the operating condition of heat pump water heater
Check the hot water amount in the cylinder
Check the setting of hot water temperature
by remote control
Readjustment of setting
contents due to increasing
hot water amount
YES
Check water pressure and water volume
NO
NO
YES
NO
Since the usage of ho water
amount seems to be very
much, the setting contents
by remote control shall be
readjusted.
①
Start and/or end time
②
Hot water amount and/or
the amount to top up
Usage of hot water amount
is too much
Check water circuit
Leak, Drain, by-pass,
Clogging,
operation of pump and
actuation of valves
Check water circuit
Go to P age
. E rror detection method
. Condition of error displayed
. P resumable cause
・
Anomaly of water circuit
between the heat pump water
heater and HW storage unit.
・
P iping failure in the HW
storage unit
N ote:
Error code
Remote control:
7-segment display:
LED
Green
Red
Heat pump
water heater
Keep
flashing
Content
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...