'15 • HM-T-246
2.9 Control
(1) Functional components for refrigerant cycle
Symbol
N ame of component
Function
Details
CM
Inverter scrotary compressor
The compressor speed is controlled to maintain nominal heating capacity
water outlet temperature set by remote control.
-
Control range of compressor speed: -0rps
The target speed of compressor can be checked with MenteP C.
FMo,
Fan motor
Low pressure control is done by fan speed.
-
-
The fan speed is controlled to maintain the low pressure .± 0.MP a.
Control range of fan speed: 0-000rpm
E E V G
E lectronic expansion valve for
gas cooler
E E V Gis used for discharge pipe temperature control
Snow protection control is done by fan rotation.
If outdoor air temperature is ° C or lower and during 0 minutes period after st
opping fan motor, fan rotates at 00min
-
for 0 minutes.
The target temperature of discharge pipe is decided by outdoor air temperature,
feed water inlet temperature and hot water outlet temperature set by remote control.
-
Control range of target discahrge pipe temperature: -° C
The target discharge pipe temperature can be checked with MenteP C.
E E V H,
E lectronic expansion valve for
air heat exchanger
E E V H, are used for low pressure control and suction superheat control of
compressor
-
Control range of suction superheat: -degC
SV -IN J
Solenoid valve for injection
Refrigerant gas from receiver is injected to the intermediate pressure port of
compressor.
P age
If gas refrigerant injection is required, SV -IN J is opened.
Injection circuit
As for the detail of gas injection control, please refer to [Injection control].
SV HG
Solenoid valve for hot gas
bypass
During defrost control, SV HG is opened.
P age
As for the detail of defrost control, please refer to [Defrost control].
SV -OIL
Solenoid valve for oil
separator
SV -OIL is used for oil return control from oil separator.
If compressor is ON and outdoor air temperature is -° C or higher, SV - OIL is
opened.
-
H-
High pressure switch
H- is used for the detection of high pressure anomaly.
When H- is opened, it makes the compressor stopped.
P age
As for the contents of high pressure anomaly detection control, please refer
to [High pressure protection control].
P SH
High pressure sensor
P SH is used for high pressure protection control and the detection of high
pressure anomaly.
P age
As for the contents of high pressure anomaly detection control and high
pressure protection control, please refer to [High pressure protection control].
P SL
Low pressure sensor
P SL is used for fan control, suction superheat control, low pressure
protection control and the detection of low pressure anomaly.
P age
As for the contents of low pressure protection control, please refer to [Low
pressure protection control].
P SM
Intermediate pressure sensor
P SM is used for open/close control of injection circuit.
P age
As for the detail of injection control, please refer to [Injection control].
Tho-A
Outdoor air temperature sensor Tho-A is used for compressor control, anti-freeze control of water pipe and
E E V control.
-
Tho-C
Under-dome temperature sensor Tho-C is used for under-dome temperature protection control.
P age
Tho-D
Discharge pipe temperature sensor Tho-D is used for discharge pipe temperature control, discharge pipe temperature
protection control and detection of discharge pipe temperature anomaly.
P age
As for the contents of discharge pipe temperature anomaly detection control and
discharge pipe temperature protection control, please refer to [Discharge pipe
temperature protection control].
Tho-G,
temperature sensor at inlet and
outlet port of gas cooler
Tho-G, are used for checking the operation status.
-
Tho-G, can be checked with MenteP C.
Tho-IN J
temperature sensor at inlet
injection port
Tho-IN J is used for checking the operation status.
-
-
Tho-IN J can be checked with MenteP C.
Tho-M
temperature sensor at inlet port of
intermediate pressure receiver
Tho-M is used for checking the operation status.
Tho-M can be checked with MenteP C.
Tho-P
P ower transistor temperature
sensor
Tho-P is used for power transistor temperature protection control.
P age
As for the contents of power transistor temperature protection contro l, please refer
to [P ower transistor temperature protection control].
Tho-R,,, temperature sensor at inlet and
outlet port of air heat exchanger
Tho-R, , , are used for defrost control and oil return control.
-
Tho-S
Suction pipe temperature sensor Tho-S is used for suction superheat control
-
0
CH
Crankcase heater
CH is used for warming up the compressor
-
DH
H
Drain pan heater
Anti-freezing heater
DH is used for preventing from freezing drain pan
-
-
If outdoor air temperature is ° C or lower and outdoor unit is in operation mode
during
minutes period after finishing defrosto operation, or during snow protection
control, DH is energized.
H is used for preventing from freezing water pipings.
If outdoor air temperature is ° C or lower and heat pump water heater is off, H is energyized.
according to the outdoor air temperature, feed water inlet temperature and hot
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...