For air purge
For drainage
(5) Replacement procedure of water heat exchanger (Gas cooler)
For air purge
For drainage
(a) Removal of residual water in the water heat exchanger
1) Remove residual water in the water heat exchanger (from 2 ports)
Turn the air purge valve and drain valve to open fully
and discharge residual water
Lever
Button
2) Turn the lever to open the flow regulator manually
While pressing the button for switching to manual
operation located at the bottom of the flow regulator,
turn the lever to open (" O" ) side.
The flow regulator shall be open, when discharging
residual water.