'15 • HM-T-246
(e) Hot water outlet temperature: 90˚C
Hot water outlet temperature: 90
Heating capacity
Power consumption
COP
Feed water temperature
Outdoor air temperature
kW
kW
5
25
30.0
8.86
3.39
16
30.0
8.99
3.34
7
30.0
9.24
3.25
2
30.0
11.05
2.71
-7
30.0
10.73
2.80
-10
28.5
10.88
2.62
-20
24.0
11.22
2.14
-25
21.0
10.86
1.93
17
25
30.0
9.46
3.17
16
30.0
9.80
3.06
7
30.0
9.89
3.03
2
30.0
11.97
2.51
-7
30.0
11.57
2.59
-10
28.5
11.84
2.41
-20
24.0
12.02
2.00
-25
21.0
11.65
1.80
24
25
30.0
10.38
2.89
16
30.0
10.62
2.82
7
30.0
10.85
2.76
2
30.0
12.62
2.38
-7
30.0
12.26
2.45
-10
28.5
12.42
2.29
-20
24.0
12.53
1.92
-25
21.0
12.20
1.72
30
25
26.0
10.55
2.47
16
26.0
10.70
2.43
7
26.0
11.16
2.33
2
30.0
13.09
2.29
-7
28.0
13.19
2.12
-10
26.5
12.97
2.04
-20
22.0
12.48
1.76
-25
20.0
12.32
1.62
<N otes> () The data of power consumption in this table do not include the power consumption of anti-freezing heater (W) .
In case of outdoor air temperature
≦
C° , please take account of the power consumption for anti-freezing heater.
() For the data of the table and the curve the performance decrement of defrost operation are considered.
But heating performance may change in climate condition and installation environment.
() In water temperature is C° or more, heating capacity is further reduced. P lease refer to the heating performance characteristics for
the recirculation system in reference.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for ESA30E-25
Page 69: ... 15 HM T 246 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 71: ... 15 HM T 246 0 WARNING CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 85: ... 15 HM T 246 4 3 System diagram 㪄㪈㪌㪄 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 91: ... 15 HM T 246 0 CAUTION AMP Air Conditioning www ampair co uk sales ampair co uk ...