3) Brazing
①
Discharge pipe
③
Gas injection pipe
②
Suction pipe
Be sure to do masking around the brazing place.
(The places not only around discharge pipe but also around
suction pipe and gas injection pipe)
N ote: Be careful to braze pipes without any gas leak later on,
because the pipe is thicker and pipe insertion depth is
deeper and then upper space is rather tight for brazing
work.