0
-
'15 • HM-T-246
(3) Compressor stop factor
(i)
Compressor stop factor () is caused by HP protection control. This control is caused by lack of supply water due to pipe
clogging.
This control can be seemed in hot season.
1.
1.Comp stop factor(Outline)
Comp stop factor(Outline)
・It can be confirmed the number of comp stop factor from mente PC or 7seg
display(C88).
・Comp stop factor is remained until occuring next stop factor.
Comp stop factor is remained until occuring next stop factor.
【Example】
・Comp stop(55) is
caused by HP protection
control This control is
91(compressor stop
for fan control)
91( compressor
stop for fan control )
Compressor stop factor
control. This control is
caused by lack of supply
water due to pipe clogging.
・Comp stop(91) is
caused by outdoor fan
t l (2 f
1f
)
55(comp sso
C
control . (2 fan → 1fan)
This control can be seemed
in hot season.
55(compressor
stop for HP
protection)
Compressor stop
factor is remained
until occuring next
stop factor.
55(compressor
stop for HP
protection)