Step 6.
Align the board-to-board connector
1
on the bottom of the memory module with the connector
2
on the ServeRAID adapter. Ensure that the three mounting studs on the ServeRAID adapter are
aligned with the corresponding holes in the memory module. Carefully press the memory module
onto the ServeRAID adapter until the two connectors (
1
and
2
) are firmly joined.
Figure 46. ServeRAID adapter memory module installation
Step 7.
Reinstall the ServeRAID adapter. See “Installing an adapter” on page 111.
Step 8.
Complete the parts replacement. See “Completing the parts replacement” on page 172.
Removing a RAID adapter battery or flash power module
Note:
The RAID adapter battery or flash power module is supported on the 2.5-inch-drive server models only.
To remove a RAID adapter battery or flash power module, do the following:
Step 1.
Turn off the server. Then, disconnect all external cables and remove all peripheral devices.
Step 2.
Remove the server cover. See “Removing the server cover” on page 88.
114
Lenovo System x3250 M6 Installation and Service Guide
Summary of Contents for x3250 m6
Page 1: ...Lenovo System x3250 M6 Installation and Service Guide Machine Types 3633 and 3943 ...
Page 6: ...iv Lenovo System x3250 M6 Installation and Service Guide ...
Page 18: ...4 Lenovo System x3250 M6 Installation and Service Guide ...
Page 60: ...46 Lenovo System x3250 M6 Installation and Service Guide ...
Page 100: ...86 Lenovo System x3250 M6 Installation and Service Guide ...
Page 516: ...502 Lenovo System x3250 M6 Installation and Service Guide ...
Page 678: ...664 Lenovo System x3250 M6 Installation and Service Guide ...
Page 685: ...Taiwan Class A compliance statement Appendix E Notices 671 ...
Page 695: ......
Page 696: ......