CAUTION: Before you begin installing the switch, ensure that a licensed electrician has
attached an appropriate grounding lug to the grounding cable that you supply. Using a
grounding cable with an incorrectly attached lug can damage the switch.
NOTE: QFX10000-PWR-DC power supplies are shipped only in the redundant configuration of
QFX10000 switches. For details about different chassis configurations, see
QFX10008
Configurations and Upgrade Options
and
"QFX10016 Components and Configurations" on page
Each QFX10000-PWR-DC power supply weighs approximately 6 lb (2.7 kg) and has two independent
pairs of DC input lugs (Input 1, RTN, –48V/–60V and Input 2, RTN, –48V/–60V) on the faceplate of the
power supply. Each inlet requires a dedicated DC power feed. Although each inlet provides sufficient
input power to provide full output, always connect to a dedicated DC power feed to provide
redundancy. Only one power feed is operational at a time.
DC power models employ electronic A-B input selection. It provides 2
n source redundancy and n+1
power supply redundancy using fewer power supplies than you would require in a 2
n configuration.
Should one power source fail, electronic A-B input selection switches the power supply to the alternate
source.
70
Summary of Contents for QFX10016
Page 1: ...QFX10016 Switch Hardware Guide Published 2022 09 09...
Page 10: ...Compliance Statements for Environmental Requirements 428 x...
Page 15: ...Figure 1 on page 5 shows a front and rear view of the QFX10016 4...
Page 16: ...Figure 1 QFX10016 Front and Rear 5...
Page 239: ...RELATED DOCUMENTATION QFX10008 Installation Overview QFX10002 System Overview 228...
Page 270: ...1 ESD point Figure 113 ESD Point on QFX10016 Chassis Rear 1 ESD point 259...
Page 287: ...Figure 130 Installing a JNP10K PWR AC2 in a QFX10016 276...
Page 322: ...Figure 159 Installing a JNP10K PWR DC2 in QFX10016 311...
Page 366: ...5 CHAPTER Troubleshooting Troubleshooting QFX10000 Modular Chassis 356...