8 Diagnosis / error messages
72
8.3 Overview
Errors encountered are itemized in tabular form on the following pages. The response of the transmitter on error detection is described
therein.
The table lists all possible errors together with a description of their impact on the value of measurement variables, the properties of
current outputs and the alarm output.
Error no. /
Area
Text on the LCD display
Current output
Digital output
Pulse output
LCD display
Maskable error?
F099.042 /
Electronics
ADC overrange alarm.
Noise too high. Check applicati.
Call service.
High Alarm or Low
Alarm depends on the
“Curr.Out at Alarm”
parameter setting.
General Alarm, if the
digital output has
been configured as a
“Logic / Alarm Signal”.
0
0 %
No
F098.012 /
Electronics
FEB communication error.
EMC disturbance. Call Service.
0
0 %
No
F097.029 /
Electronics
Coil regulation error.
Check wiring of sensor coils.
Call service
0
0 %
No
F096.043 /
Electronics
SIL self check alarm.
Call service.
No change; current
value.
No change; current
value.
No
F095.036 /
Electronics
Coil isolation alarm.
Call service.
No change; current
value.
No change; current
value.
No
F094.022 /
Electronics
Safety Alarm Curr. Out 31 / 32
SIL function detects error. Call
Service.
No change; current
value.
No change; current
value.
No
F093.032 /
Electronics
Electrode short cuircit.
Check wiring of sensor
electrode. Call service.
0
0 %
No
F092.033 /
Electronics
Electrode open cuircit.
Check wiring of sensor
electrode. Call service.
0
0 %
No
F091.030 /
Electronics
Coil wiring error.
Check wiring of sensor coils.
Call service.
0
0 %
No
F090.035 /
Electronics
ADC RX210 com. error.
Call service.
0
0 %
No
F088.013 /
Electronics
FEB communication error.
EMC disturbance. Call Service.
0
0 %
No
F086.019 /
Electronics
Curr.Out 31 / 32 com error.
Defective Board. EMC
disturbance. Call Service.
No change; current
value.
No change; current
value.
No
F084.011 /
Electronics
NV data defect.
Data storage irreparable. Call
Service.
0
0 %
No
F082.014 /
Electronics
Incompatible Frontend Board.
Frontend not fit to Motherboard.
Call Service.
0
0 %
No
F081.026 /
Electronics
MB voltages outside range.
Defective Motherboard HW. Call
Service.
0
0 %
No
Summary of Contents for 406060
Page 2: ......
Page 98: ...13 Appendix 98 13 3 Declarations of conformity 13 3 1 JUMO flowTRANS MAG S10...
Page 99: ...13 Appendix 99...
Page 100: ...13 Appendix 100...
Page 101: ...13 Appendix 101...
Page 102: ...13 Appendix 102...
Page 103: ...13 Appendix 103...
Page 104: ...13 Appendix 104 13 3 2 JUMO flowTRANS MAG H10...
Page 105: ...13 Appendix 105...
Page 106: ...13 Appendix 106...
Page 107: ...13 Appendix 107...
Page 108: ...13 Appendix 108...
Page 109: ...13 Appendix 109...
Page 110: ...13 Appendix 110 13 3 3 JUMO flowTRANS MAG 10...
Page 111: ...13 Appendix 111...
Page 112: ...13 Appendix 112...
Page 113: ...13 Appendix 113...
Page 115: ......