5 Installation
34
Transmitter
1
Terminals for power supply
2
Terminals for inputs and outputs
3
Terminals for signal cable
4
Cable entry for inputs and outputs
5
Cable entry for signal cable
6
Terminal for equipotential bonding
7
Cable entry for power supply
Figure 42: Electrical transmitter connection for remote mount design (example)
Change from one to two columns
NOTICE
If the O-ring gasket is seated incorrectly or damaged, this
may have an adverse effect on the housing protection
class.
Follow the instructions in
Opening and closing the terminal
box
on page 22 to open and close the housing safely.
Compliance with the information below is required for making the
electrical connections:
• Route the power supply cable and the cable for the signal
inputs and outputs into the housing as shown.
• Connect the cables in accordance with the connection
diagrams. Connect the cable shields (if applicable) to the
provided grounding clamp.
• Use ferrules for making the connections.
• Use suitable plug(s) to seal the cable entries that are not
used.
Note
• Adhere to the limit values of the power supply in accordance
with the information on the name plate.
• Observe the voltage drop for large cable lengths and small
conductor cross-sections. The voltage at the terminals of the
device may not down-scale the minimum value required in
accordance with the information on the name plate.
The power supply is connected to terminal L (phase), N (zero), or
1+, 2
−
, and PE.
A circuit breaker with a maximum rated current of 16 A must be
installed in the power supply line.
The wire cross-sectional area of the power supply cable and the
circuit breaker used must comply with VDE 0100 and must be
dimensioned in accordance with the current consumption of the
flowmeter measuring system. The cables must comply with IEC
227 and/or IEC 245.
The circuit breaker must be located near the device and marked
as being associated with the device.
Connect the transmitter and sensor to functional earth.
Change from two to one column
Summary of Contents for 406060
Page 2: ......
Page 98: ...13 Appendix 98 13 3 Declarations of conformity 13 3 1 JUMO flowTRANS MAG S10...
Page 99: ...13 Appendix 99...
Page 100: ...13 Appendix 100...
Page 101: ...13 Appendix 101...
Page 102: ...13 Appendix 102...
Page 103: ...13 Appendix 103...
Page 104: ...13 Appendix 104 13 3 2 JUMO flowTRANS MAG H10...
Page 105: ...13 Appendix 105...
Page 106: ...13 Appendix 106...
Page 107: ...13 Appendix 107...
Page 108: ...13 Appendix 108...
Page 109: ...13 Appendix 109...
Page 110: ...13 Appendix 110 13 3 3 JUMO flowTRANS MAG 10...
Page 111: ...13 Appendix 111...
Page 112: ...13 Appendix 112...
Page 113: ...13 Appendix 113...
Page 115: ......