7 Operation
45
7.3.3 Error messages on the LCD display
In the event of an error, a message consisting of a symbol and
text (e.g. Electronics) appears at the bottom of the process
screen.
The text displayed provides information about the area in which
the error has occurred.
Process display
Electronics
The error messages are divided into four groups in accordance
with the NAMUR classification scheme. The group assignment
can only be changed using a DTM or EDD:
Symbol Description
Error / failure
Function check
Outside of the specification
Maintenance required
The error messages are also divided into the following areas:
Range Description
Operation
Error / alarm due to the current operating conditions.
Sensor
Error / alarm of the flowmeter sensor.
Electronics
Error / alarm of the electronics.
Configuration
Error / alarm due to device configuration.
Note
For a detailed description of errors and troubleshooting
instructions, please see
Diagnosis / error messages
on
page 68.
7.3.4 Switching to the configuration level
(parameterization)
The device parameters can be displayed and changed on the
configuration level.
Process display
1.
Use
to go to the configuration level.
Access Level
Read Only
Standard
Service
Back
Select
2.
Use
/
to select the required access level.
3.Use
to confirm your selection.
Note
There are three access levels. A password can be specified for
the “Standard” level.
There is no factory default password.
Access Level
Description
Read Only
All parameters are blocked. Parameters can only be
read and not modified.
Standard
All parameter settings can be changed.
Service
The Service menu is reserved solely for the customer
service department of the manufacturer.
Summary of Contents for 406060
Page 2: ......
Page 98: ...13 Appendix 98 13 3 Declarations of conformity 13 3 1 JUMO flowTRANS MAG S10...
Page 99: ...13 Appendix 99...
Page 100: ...13 Appendix 100...
Page 101: ...13 Appendix 101...
Page 102: ...13 Appendix 102...
Page 103: ...13 Appendix 103...
Page 104: ...13 Appendix 104 13 3 2 JUMO flowTRANS MAG H10...
Page 105: ...13 Appendix 105...
Page 106: ...13 Appendix 106...
Page 107: ...13 Appendix 107...
Page 108: ...13 Appendix 108...
Page 109: ...13 Appendix 109...
Page 110: ...13 Appendix 110 13 3 3 JUMO flowTRANS MAG 10...
Page 111: ...13 Appendix 111...
Page 112: ...13 Appendix 112...
Page 113: ...13 Appendix 113...
Page 115: ......