5 Installation
27
5.5.2 Installing the connecting cables
Compliance with the following items is required when routing
signal cables:
• A magnetic coil cable (red and brown) is run parallel to the
signal lines (violet and blue). As a result, only one cable is
required between the sensor and the transmitter. Do not
use junction boxes or terminal strips for routing cables.
• The signal cable carries a voltage signal of only a few
millivolts and must, therefore, be routed over the shortest
possible distance. The maximum permissible signal cable
length is 50 m (164 ft).
• Avoid routing the cable in the vicinity of electrical
equipment or switching elements that can create stray
fields, switching pulses and induction. If this is not
possible, run the signal / magnetic coil cable through a
metal pipe and connect this to the station ground
potential.
• All leads must be shielded and connected to the station
ground potential.
• The cable contains outer shielding to shield against
magnetic interspersion. Connect this at the SE terminal.
• Also connect the supplied stranded steel wire to the SE
terminal.
• Do not damage the sheathing of the cable during
installation.
• Make provisions for a drip loop (water trap) when
installing the connecting cables for the sensor.
1
Drip loop
Figure 32: Installing the connection cables
5.5.3 Connection via cable conduit
Figure 33: Installation set for cable conduit
NOTE
Condensate formation in terminal box.
If the sensor is permanently connected to cable conduits, there
is a possibility that moisture may get into the terminal box as a
result of condensate formation in the cable conduit.
Ensure that the cable entry points on the terminal box are
sealed.
An installation set for sealing the cable conduit (Conduit) is
available via part no. 00645908.
Summary of Contents for 406060
Page 2: ......
Page 98: ...13 Appendix 98 13 3 Declarations of conformity 13 3 1 JUMO flowTRANS MAG S10...
Page 99: ...13 Appendix 99...
Page 100: ...13 Appendix 100...
Page 101: ...13 Appendix 101...
Page 102: ...13 Appendix 102...
Page 103: ...13 Appendix 103...
Page 104: ...13 Appendix 104 13 3 2 JUMO flowTRANS MAG H10...
Page 105: ...13 Appendix 105...
Page 106: ...13 Appendix 106...
Page 107: ...13 Appendix 107...
Page 108: ...13 Appendix 108...
Page 109: ...13 Appendix 109...
Page 110: ...13 Appendix 110 13 3 3 JUMO flowTRANS MAG 10...
Page 111: ...13 Appendix 111...
Page 112: ...13 Appendix 112...
Page 113: ...13 Appendix 113...
Page 115: ......