Goodrive200 inverters Function codes
51
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Modify the function code to shift the rotation
direction of the motor. This effect equals to the
shifting the rotation direction by adjusting either
two of the motor lines (U, V and W). In keypad
control, the motor rotation direction can be
changed by QUICK/JOG on the keypad. Refer to
parameter P07.02.
Note:
When the function parameter comes back
to the default value, the motor’s running direction
will come back to the factory default state, too. In
some cases it should be used with caution after
commissioning if the change of rotation direction
is disabled.
2: Forbid to run in reverse direction: It can be
used in some special cases if the reverse running
is disabled.
P00.14
Carrier
frequency
setting
The relationship table of the motor type and
carrier frequency:
Model
Factory setting of
carrier frequency
1.5~11kW
8kHz
15~55kW
4kHz
Above 75kW
2kHz
The advantage of high carrier frequency: ideal
Depend
on
model
○
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...