Goodrive200 inverters Function codes
76
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
filter time terminals. If the interference is strong, increase
the parameter to avoid the disoperation.
0.000~1.000s
P05.12
Virtual
terminals
setting
0x000~0x1FF(0: Disabled, 1:Enabled )
BIT0:S1
virtual terminal
BIT1:S2
virtual terminal
BIT2:S3
virtual terminal
BIT3:S4
virtual terminal
BIT4:S5
virtual terminal
BIT5:S6
virtual terminal
BIT6:S7
virtual terminal
BIT7:S8
virtual terminal
BIT8:HDI
virtual terminal
0x000
◎
P05.13
Terminals
control
running
mode
Set the operation mode of the terminals control
0:2-wire control 1, comply the enable with the
direction. This mode is widely used. It determines
the rotation direction by the defined FWD and
REV terminals command.
FWD
REV
COM
K1
K2
Running
command
FWD
REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stopping
Hold on
Forward
running
Reverse
running
1:2-wire control 2; Separate the enable from the
direction. FWD defined by this mode is the
enabling ones. The direction depends on the
state of the defined REV.
0
◎
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...