Goodrive200
inverters Communication protocol
223
checkout is applied, the even check bit is “1”; if the odd checkout is applied; the odd check bit
is “0”. The even and odd check bit is calculated on the check bit position of the frame. And
the receiving devices also carry out even and odd checkout. If the parity of the receiving data
is different from the setting value, there is an error in the communication.
CRC check
The checkout uses RTU frame format. The frame includes the frame error detection field
which is based on the CRC calculation method. The CRC field is two bytes, including 16
figure binary values. It is added into the frame after calculated by transmitting device. The
receiving device recalculates the CRC of the received frame and compares them with the
value in the received CRC field. If the two CRC values are different, there is an error in the
communication.
During CRC, 0*FFFF will be stored. And then, deal with the continuous 6-above bytes in the
frame and the value in the register. Only the 8Bit data in every character is effective to CRC,
while the start bit, the end and the odd and even check bit is ineffective.
The calculation of CRC applies the international standard CRC checkout principles. When
the user is editing CRC calculation, he can refer to the relative standard CRC calculation to
write the required CRC calculation program.
Here provided a simple function of CRC calculation for the reference (programmed with C
language):
unsigned int crc_cal_value(unsigned char *data_value,unsigned char data_length)
{
int i;
unsigned int crc_value=0xffff;
while(data_length--)
{ crc_value^=*dat+;
for(i=0;i<8;i++)
{
if(crc_value&0x0001)crc_value=(crc_value>>1)^0xa001;
else crc_value=crc_value>>1;
} }
return(crc_value);
}
In ladder logic, CKSM calculated the CRC value according to the frame with the table inquiry.
The method is advanced with easy program and quick calculation speed. But the ROM
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...