Goodrive200 inverters Fault tracking
204
Fault code
Fault type
Possible cause
What to do
PIDE
PID feedback fault
PID feedback offline
PID feedback source
disappear
Check the PID feedback
signal
Check the PID feedback
source
bCE
Braking unit fault
Braking circuit fault or
damage to the braking
pipes
The external braking
resistor is not sufficient
Check the braking unit and
change new braking pipe
Increase the braking
resistor
ETH1
Grounding
shortcut fault 1
The output of the inverter
is short circuited with the
ground
There is fault in the current
detection circuit
The actual motor power
sharply differs from the
inverter power
Check if the connection of
the motor is normal or not
Change the hoare
Change the main control
panel
Set motor parameters
correctly
ETH2
Grounding
shortcut fault 2
The output of the inverter
is short circuited with the
ground
There is fault in the current
detection circuit
The actual motor power
sharply differs from the
inverter power
Check if the connection of
the motor is normal or not
Change the hoare
Change the main control
panel
Set motor parameters
correctly
dEu
Velocity deviation
fault
The load is too heavy or
stalled
Check the load and
ensure it is normal
Increase the detection
time
Check whether the control
parameters are normal
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...