Goodrive200
inverters Product overview
16
3.5 Type designation key
The type designation contains information on the inverter. The user can find the type
designation on the type designation label attached to the inverter or the simple name plate.
Fig 3-4 Product type
Key
Instructions
A
GD200: abbreviation of Goodrive200
B, D
3-digit code: output power. “R” means the decimal point; ”011”:11kW;
“015”:15kW
C, E
C
G:Constant torque load
E
P:Variable torque load
F
Input voltage degree:
2: AC 3PH 220V(-15%)~240V(+10%)
4: AC 3PH 380V(-15%)~ 440V(+10%)
6: AC 3PH 520V(-15%)~690V(+10%)
3.6 Rated specifications
Model
Constant torque
Variable torque
Output
power
(kW)
Input
current
(A)
Output
current
(A)
Output
power
(kW)
Input
current
(A)
Output
current
(A)
GD200-1R5G-4
1.5
5.0
3.7
GD200-2R2G-4
2.2
5.8
5
GD200-004G/5R5P-4
4
13.5
9.5
5.5
19.5
14
GD200-5R5G/7R5P-4
5.5
19.5
14
7.5
25
18.5
GD200-7R5G/011P-4
7.5
25
18.5
11
32
25
GD200-011G/015P-4
11
32
25
15
40
32
GD200-015G/018P-4
15
40
32
18.5
47
38
GD200-018G/022P-4
18.5
47
38
22
56
45
GD200-022G/030P-4
22
56
45
30
70
60
GD200-030G/037P-4
30
70
60
37
80
75
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...