Goodrive200 inverters Installation guidelines
33
Terminal
name
Description
RO1A
RO1 relay output, RO1A NO, RO1B NC, RO1C common terminal
Contactor capability: 3A/AC250V,1A/DC30V
RO1B
RO1C
RO2A
RO2 relay output, RO2A NO, RO2B NC, RO2C common terminal
Contactor capability: 3A/AC250V,1A/DC30V
RO2B
RO2C
Terminal
name
Description
PE
Grounding terminal
PW
Provide the input switch working power supply from external to
internal.
Voltage range: 12~24V
24V
The inverter provides the power supply for users with a maximum
output current of 200mA
COM
+24V common terminal
S1
Switch input 1
1. Internal impedance:3.3kΩ
2. 12~30V voltage input is available
3. The terminal is the dual-direction input
terminal supporting both NPN and PNP
4. Max input frequency:1kHz
5. All are programmable digital input
terminal. User can set the terminal function
through function codes.
S2
Switch input 2
S3
Switch input 3
S4
Switch input 4
S5
Switch input 5
S6
Switch input 6
S7
Switch input 7
S8
Switch input 8
HDI
Except for S1~S8, this terminal can be used as high frequency
input channel.
Max. input frequency:50kHz
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...