Goodrive200 inverters Function codes
114
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
adjustment LED ones:
0: Keep on integral adjustment when the
frequency achieves the upper and low limit; the
integration shows the change between the
reference and the feedback unless it reaches the
internal integral limit. When the trend between
the reference and the feedback changes, it
needs more time to offset the impact of
continuous working and the integration will
change with the trend.
1: Stop integral adjustment when the frequency
achieves the upper and low limit. If the integration
keeps stable, and the trend between the
reference and the feedback changes, the
integration will change with the trend quickly.
LED tens: P00.08 is 0
0: The same with the setting direction; if the
output of PID adjustment is different from the
current running direction, the internal will output 0
forcedly.
1:Opposite to the setting direction
LED hundreds: P00.08 is 0
0: Limit to the maximum frequency
1: Limit to frequency A
LED thousands:
0:A+B frequency, the buffer of A frequency is
invalid
1:A+B frequency, the buffer of A frequency is
valid
ACC/DEC is determined by ACC time 4 of
P08.04
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...