Goodrive200
inverters Communication protocol
221
Code system
·
1 start bit
·
7 or 8 digital bit, the minimum valid bit can be sent firstly. Every 8 bit frame includes two
hex characters (0...9, A...F)
·
1 even/odd check bit . If there is no checkout, the even/odd check bit is inexistent.
·
1 end bit (with checkout), 2 Bit(no checkout)
Error detection field
·
CRC
The data format is illustrated as below:
11-bit character frame (BIT1~BIT8 are the digital bits)
Start bit
BIT1
BIT2
BIT3
BIT4
BIT5
BIT6
BIT7
BIT8
Check
bit
End bit
10-bit character frame (BIT1~BIT7 are the digital bits)
Start bit
BIT1
BIT2
BIT3
BIT4
BIT5
BIT6
BIT7
Check
bit
End bit
In one character frame, the digital bit takes effect. The start bit, check bit and end bit is used
to send the digital bit right to the other device. The digital bit, even/odd checkout and end bit
should be set as the same in real application.
The MODBUS minimum idle time between frames should be no less than 3.5 bytes. The
network device is detecting, even during the interval time, the network bus. When the first
field (the address field) is received, the corresponding device decodes next transmitting
character. When the interval time is at least 3.5 byte, the message ends.
The whole message frame in RTU mode is a continuous transmitting flow. If there is an
interval time (more than 1.5 bytes) before the completion of the frame, the receiving device
will renew the uncompleted message and suppose the next byte as the address field of the
new message. As such, if the new message follows the previous one within the interval time
of 3.5 bytes, the receiving device will deal with it as the same with the previous message. If
these two phenomena all happen during the transmission, the CRC will generate a fault
message to respond to the sending devices.
The standard structure of RTU frame:
START
T1-T2-T3-T4(transmission time of 3.5 bytes)
ADDR
Communication address: 0~247(decimal system)(0 is the broadcast
address)
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...