Goodrive200
inverters Communication protocol
230
Function
instruction
Address
definition
Data meaning instruction
R/W
characteristics
corresponds to the 100.0% of the rated current
of the motor)
2005H
The upper limit frequency setting during
forward rotation(0~Fmax(unit: 0.01Hz))
W/R
2006H
The upper limit frequency setting during
reverse rotation(0~Fmax(unit: 0.01Hz))
W/R
2007H
The upper limit torque of electromotion torque
(0~3000, 1000 corresponds to the 100.0% of
the rated current of the motor)
W/R
2008H
The upper limit torque of braking torque
(0~3000, 1000 corresponds to the 100.0% of
the rated current of the motor)
W/R
2009H
Special control command word
Bit0~1:=00:motor 1 =01:motor 2
=10:motor 3 =11:motor 4
Bit2:=1 torque control =0:speed control
W/R
200AH
Virtual input terminal command , range:
0x000~0x1FF
W/R
200BH
Virtual input terminal command , range:
0x00~0x0F
W/R
200CH
Voltage setting value(special for V/F
separation)
(0~1000, 1000 corresponds to the 100.0% of
the rated voltage of the motor)
W/R
200DH
AO output setting 1(-1000~1000, 1000
corresponds to 100.0%)
W/R
200EH
AO output setting 2(-1000~1000, 1000
corresponds to 100.0%)
W/R
SW 1 of the
inverter
2100H
0001H:forward running
R
0002H:forward running
0003H:stop
0004H:fault
0005H: POFF state
SW 2 of the
inverter
2101H
Bit0: =0:bus voltage is not established
=1:bus voltage is established
Bi1~2:=00:motor 1 =01:motor 2
=10:motor 3 =11:motor 4
Bit3: =0:asynchronous motor
=1:synchronous motor
Bit4:=0:pre-alarm without overload
R
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...