Goodrive200
inverters Communication protocol
225
that the high bit is in the front and the low bit is in the behind.
“Data number”
means the reading data number with the unit of word. If the “start address’ is
0004H and the “data number” is 0002H, the data of 0004H and 0005H will be read.
CRC
occupies 2 bytes with the fact that the high bit is in the front and the low bit is in the
behind.
RTU
slave response message (from the inverter to the master)
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
01H
CMD
03H
Byte number
04H
Data high bit of address 0004H
13H
Data low bit of address 0004H
88H
Data high bit of address 0005H
00H
Data low bit of address 0005H
00H
CRC CHK low bit
7EH
CRC CHK high bit
9DH
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
The meaning of the response is that:
ADDR
= 01H means the command message is sent to the inverter with the address of 01H
and ADDR occupies one byte
CMD
=03H means the message is received from the inverter to the master for the response
of reading command and CMD occupies one byte
“Byte number”
means all byte number from the byte(excluding the byte) to CRC
byte(excluding the byte). 04 means there are 4 byte of data from the “byte number” to “CRC
CHK low bit”, which are “digital address 0004H high bit”, “digital address 0004H low bit”,
“digital address 0005H high bit” and “digital address 0005H low bit”.
There are 2 bytes stored in one data with the fact that the high bit is in the front and the low
bit is in the behind of the message, the data of data address 0004H is 1388H, and the data
of data address 0005H is 0000H.
CRC occupies 2 bytes with the fact that the high bit is in the front and the low bit is in the
behind.
10.4.2 Command code: 06H
06H (correspond to binary 0000 0110), write one word(Word)
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...