Goodrive200 inverters Function codes
115
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P09.14
Proportion
al gain at
low
frequency
(Kp)
0.00~100.00
1.00
○
P09.15
PID
command
of
ACC/DEC
time
0.0~1000.0s
0.0s
○
P09.16
PID output
filter time
0.000~10.000s
0.000s
○
P10 Group Simple PLC and multi-step speed control
P10.00
Simple
PLC
0: Stop after running once. The inverter has to be
commanded again after finishing a cycle.
1: Run at the final value after running once. After
finish a signal, the inverter will keep the running
frequency and direction of the last run.
2: Cycle running. The inverter will keep on
running until receiving a stop command and then,
the system will stop.
0
○
P10.01
Simple
PLC
memory
0: Power loss without memory
1:Power loss memory
;
PLC record the running
step and frequency when power loss.
0
○
P10.02
Multi-step
speed 0
100.0% of the frequency setting corresponds to
the Max. frequency P00.03.
When selecting simple PLC running, set
P10.02~P10.33 to define the running frequency
and direction of all steps.
Note:
The symbol of multi-step determines the
0.0%
○
P10.03
The
running
time of
step 0
0.0s
○
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...