Goodrive200 inverters Function codes
128
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P16 Group Ethernet function
P17 Group Monitoring function
P17.00
Setting
frequency
Display current set frequency of the inverter
Range: 0.00Hz~P00.03
●
P17.01
Output
frequency
Display current output frequency of the inverter
Range: 0.00Hz~P00.03
●
P17.02
Ramp
reference
frequency
Display current ramp reference frequency of the
inverter
Range: 0.00Hz~P00.03
●
P17.03
Output
voltage
Display current output voltage of the inverter
Range: 0~1200V
●
P17.04
Output
current
Display current output current of the inverter
Range: 0.0~3000.0A
●
P17.05
Motor
speed
Display the rotation speed of the motor.
Range: 0~65535RPM
●
P17.06
Reserved
●
P17.07
Reserved
●
P17.08
Motor
power
Display current motor power
Range:-300~300%
●
P17.09
Output
torque
Display the current output torque of the inverter.
Range: -250.0~250.0%
●
P17.10
Evaluated
motor
frequency
Evaluated frequency of motor rotor
Range: 0.00Hz~ P00.03
●
P17.11
DC bus
voltage
Display current DC bus voltage of the inverter
Range: 0.0~2000.0V
●
P17.12
ON-OFF
input
terminals
state
Display current Switch input terminals state of the
inverter
BIT8
BIT7
BIT6
BIT5
HDI
S8
S7
S6
BIT4
BIT3
BIT2
BIT1
BIT0
●
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...