Goodrive200 inverters Function codes
78
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
COM
SB2
SB1
FWD
REV
SIn
SB3
Sln
FWD
REV
Direction
ON
OFF→
ON
ON
Forward
OFF
Reverse
ON
ON
OFF→
ON
Forward
OFF
Reverse
ON→
OFF
Decelerat
e to stop
Note
:
for the 2-wire running mode, when
FWD/REV terminal is valid, the inverter stop
because of the stopping command from other
sources, even the control terminal FWD/REV
keeps valid; the inverter won
’
t work when the
stopping command is canceled. Only when
FWD/REV is relaunched, the inverter can start
again. For example, the valid STOP/RST stop
when PLC signal cycles stop, fixed-length stop
and terminal control (see P07.04).
P05.14
S1 terminal
switching-o
n delay
time
The function code defines the corresponding
delay time of electrical level of the programmable
terminals from switching on to switching off.
Setting range:0.000~50.000s
0.000s
○
P05.15
S1
terminal
switching-o
ff delay
0.000s
○
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...