Goodrive200
inverters Communication protocol
237
Function
instruction
Address
definition
Data meaning instruction
R/W
characteristics
communication
setting
frequency(0~Fmax(unit: 0.01Hz))
2002H
PID given, range(0~1000, 1000 corresponds
to100.0% )
Set P00.01 to 2 and P00.06 to 8.
The command sent to the inverter:
If the response message is as below:
Example 2: set the ACC time of 01H inverter as 10s and the DEC time as 20s
P00.11 ACC time 1
ACC time means the time needed if the inverter
speeds up from 0Hz to the Max. One (P00.03).
DEC time means the time needed if the inverter
speeds down from the Max. Output frequency to
0Hz (P00.03).
Goodrive300 series inverters define four groups of
ACC/DEC time which can be selected by P05. The
factory default ACC/DEC time of the inverter is the
first group.
Setting range of P00.11 and P00.12:0.0~3600.0s
Depend
on
model
○
P00.12 DEC time 1
Depend
on
model
○
The corresponding address of P00.11 is 000B, the ACC time of 10s corresponds to 0064H,
and the DEC time of 20s corresponds to 00C8H.
The command sent to the inverter:
If the response message is as below:
Note
: The space between above commands is for instruction and there is no space between
the commands during actual applications.
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...