Goodrive200 inverters Installation guidelines
32
4.3.5 Terminals of control circuit
Fig 4-21 Terminals of control circuit
Terminal
name
Description
+10V
Local power 10V
AI1
1. Input range: AI1/AI2 voltage and current can be chose:
0~10V/0~20Ma; AI1 can be shifted by J3; AI2 can be shifted by J4
AI3:-10V~+10V
2. Input impedance: voltage input: 20kΩ; current input: 500Ω
3. Resolution: the minimum one is 5mV when 10V corresponds to
50Hz
4. Deviation ±1%, 25
℃
AI2
AI3
GND
+10V reference null potential
AO1
1. Output range:0~10V or 0~20mA; AO1 can be shifted by J1;
AO2 can be shifted by J2
2. Deviation±1%,25
℃
AO2