Goodrive200 inverters Function codes
106
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
large, it is recommended setting range:
voltage
380V
500V
660
range
685~750V 860~950V
1080~118
0V
660V
voltage:
1120.0V
P08.39
Cooling fan
running
mode
Set the operation mode of the cooling fan.
0: Normal mode, after the rectifier receives
operation command or the detected temperature
of module is above 45
℃
or the module current is
above 20% of the rated current, the fan rotates.
1:The fan keeps on running after power on
(generally for the site with high temperature and
humidity)
0
○
P08.40
PWM
selection
0x00~0x21
LED ones: PWM mode selection
0: PWM mode 1, three-phase modulation and
two-modulation
1: PWM mode 2, three-phase modulation
LED tens: low-speed carrier frequency limit mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at
low speed
1:Low-speed carrier frequency limit mode 2, the
carrier frequency will limit to 4k if it exceeds 4k at
low speed
2: No limit
01
◎
P08.41
Over
commissio
n selection
0x00~0x11
LED ones
0: Invalid
1: Valid
LED tens
0: Light overcommission
0x01
◎
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...