Goodrive200
inverters Basic operation instruction
190
Function
code
Name
Detailed instruction of parameters
Default
value
4:High speed pulse HDI set
5:Multi-step speed set
6:MODBUS communication
7~9:Reserved
P09.01
Keypad PID preset
-100.0%~100.0%
0.0%
P09.02
PID feedback source
0:Analog channel AI1 feedback
1:Analog channel AI2 feedback
2:Analog channel AI3 feedback
3:High speed HDI feedback
4:MODBUS communication feedback
5~7:Reserved
0
P09.03
PID output feature
0:PID output is positive
1:PID output is negative
0
P09.04
Proportional gain (Kp)
0.00~100.00
1.00
P09.05
Integral time(Ti)
0.01~10.00s
0.10s
P09.06
Differential time(Td)
0.00~10.00s
0.00s
P09.07
Sampling cycle(T)
0.00~100.00s
0.10s
P09.08
PID control deviation limit 0.0~100.0%
0.0%
P09.09
Output upper limit of PID
P09.10~100.0% (Max. frequency or Max.
voltage)
100.0%
P09.10
Output lower limit of PID
-100.0%~P09.09 (Max. frequency or
Max. voltage)
0.0%
P09.11
Feedback offline detection
value
0.0~100.0%
0.0%
P09.12
Feedback offline detection
time
0.0~3600.0s
1.0s
P09.13
PID adjustment
LED ones:
0: Keep on integral adjustment when the
frequency achieves the upper and low
limit; the integration shows the change
between the reference and the feedback
0x0001
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...