Goodrive200 inverters Function codes
71
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
(the rated voltage of motor 1)
P04.09
V/F slip
compensat
ion gain of
motor 1
This function code is used to compensate the
change of the rotation speed caused by load
during compensation SVPWM control to improve
the rigidity of the motor. It can be set to the rated
slip frequency of the motor which is counted as
below:
△
f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the motor, its
function code is P02.02; n is the rated rotating
speed of the motor and its function code is
P02.03; p is the pole pair of the motor. 100.0%
corresponds to the rated slip frequency
△
f.
Setting range:0.0~200.0%
100.0%
○
P04.10
Motor 1
low
frequency
vibration
control
factor
In the SVPWM control mode, current fluctuation
may occur to the motor on some frequency,
especially the motor with big power. The motor
can not run stably or overcurrent may occur.
These phenomena can be canceled by adjusting
this parameter.
The setting range of P04.10:0~100
The setting range of P04.11:0~100
The setting range of P04.12:0.00Hz~P00.03
(the Max. frequency)
10
○
P04.11
Motor 1
high
frequency
vibration
control
factor
10
○
P04.12
Motor 1
vibration
control
threshold
30.00 Hz
○
P04.13
Reserved
◆
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...