3. Electrical Installation
- 52 -
3
Figure 3-3 Terminal dimensions of MD290T45G/55P and MD290T55G/75P
R
S
POWER
T
BR
(+)
(-)
V
U
W
MOTOR
248
11
M8 flat washer
+ spring washer
+ nut
26.8
24.8
111
31
M8
combination
screw
Table 3-4 Recommended cable dimensions and tightening torque of MD290T45G/55P and
MD290T55G/75P
AC Drive Model
Rated Input
Current (A)
Power Input/
Output Cable
Crimp
Terminal
Model
Ground
Cable
Crimp
Terminal
Model
Tightening
Torque (N·m)
Screw
Spec.
MD290T45G
89
3 x 35 mm
2
3 x 2 AWG
22-8
25 mm
2
6 AWG
14-8
10.5
M8
MD290T55P
111
3 x 50 mm
2
3 x 1/0 AWG
60-8
25 mm
2
6 AWG
14-8
10.5
M8
MD290T55G
106
3 x 50 mm
2
3 x 1/0 AWG
60-8
25 mm
2
6 AWG
14-8
10.5
M8
MD290T75P
143
3 x 70 mm
2
3 x 2/0 AWG
70-12
35 mm
2
4 AWG
22-12
10.5
M12