6. Description of Parameters
- 187 -
6
These function parameters determine active mode of VDI1 to VD15.
Ɣ
0: Decided by state of VDOx
To enable the AC drive to detect a fault and stop when input from AI1 input reaches limit,
perform the following settings:
–
6HW$WRWRVHW9',IRUIXQFWLRQ³8VHUGH¿QHGIDXOW´
–
Set A1-05 to xxx0 to determine VDI1 active state by state of VDOx.
–
Set A1-11 to 31 to set VDO1 for function 31 “AI1 input exceeding limit”.
When input from AI1 reaches limit, VDO1 becomes on. Then, VDI1 becomes on and the AC
GULYHUHFHLYHVXVHUGH¿QHGIDXOW
Ɣ
1: Decided by A1-06
To enable the AC drive to automatically enter running status after power-on, perform the
following settings:
–
Set A1-00 to 1 to set VDI1 for function 1 “Forward RUN (FWD)”.
–
Set A1-05 to xxx1 to determine VDI1 active state by state of A1-06.
–
Set F0-02 to 1 to use terminal control as command source.
–
Set F8-18 to 0 to disable start protection.
After completing initialization at power-on, the AC drive detects that VDI1 set for function
FWD is active. This means the AC drive receives forward run command from VDI1 and starts
forward running.
Summary of Contents for MD290 Series
Page 1: ......
Page 79: ...3 Electrical Installation 78 3 ...
Page 80: ...4 Operating Panel Keypad Display 4 1 Introduction 80 4 2 Inbuilt LED Operating Panel 80 ...
Page 92: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 92 5 2 Setup Flowchart 93 ...
Page 227: ...7 Interfaces and Communication 226 7 ...
Page 285: ...10 Troubleshooting 284 11 ...
Page 349: ......
Page 350: ......