6. Description of Parameters
- 145 -
6
Related parameters are described as follows:
Function Code
Parameter Name
Setting Range
Default
F1-00
Motor type selection
0: Common asynchronous motor
1: Variable frequency asynchronous motor
1
F1-01
Rated motor power
0.1 to 1000.0 kW
Model
dependent
F1-02
Rated motor voltage
1 to 2000 V
Model
dependent
F1-03
Rated motor current
WR$$&GULYHSRZHUN:
0.1 to 6553.5 A (AC drive power > 55 kW)
Model
dependent
F1-04
Rated motor
frequency
0.01 Hz to max. frequency
Model
dependent
F1-05
Rated motor speed
1 to 65535 RPM
Model
dependent
F1-00 to F1-05 are motor nameplate parameters. Set them correctly according to motor
nameplate to ensure accurate motor auto-tuning result.
Function Code
Parameter Name
Setting Range
Default
F1-06
Stator resistance
WRȍ$&GULYHSRZHUN:
WRȍ$&GULYHSRZHU!N:
Model
dependent
F1-07
Rotor resistance
WRȍ$&GULYHSRZHUN:
WRȍ$&GULYHSRZHU!N:
Model
dependent
F1-08
Leakage inductive
reactance
WRP+$&GULYHSRZHUN:
0.001 to 65.535 mH (AC drive power > 55 kW)
Model
dependent
F1-09
Mutual inductive
reactance
WRP+$&GULYHSRZHUN:
0.01 to 655.35 mH (AC drive power > 55 kW)
Model
dependent
F1-10
No-load current
WR)$&GULYHSRZHUN:
0.1 to F1-03 (AC drive power > 55 kW)
Model
dependent
F1-06 to F1-10: These function parameters are asynchronous motor parameters and can be
obtained through motor auto-tuning. Only F1-06 to F1-08 can be obtained through static auto-
tuning. F1-06 to F1-10 can be obtained through dynamic auto-tuning.
If motor auto-tuning cannot be performed on site, set these parameters according to data
provided by motor manufacturer.
Summary of Contents for MD290 Series
Page 1: ......
Page 79: ...3 Electrical Installation 78 3 ...
Page 80: ...4 Operating Panel Keypad Display 4 1 Introduction 80 4 2 Inbuilt LED Operating Panel 80 ...
Page 92: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 92 5 2 Setup Flowchart 93 ...
Page 227: ...7 Interfaces and Communication 226 7 ...
Page 285: ...10 Troubleshooting 284 11 ...
Page 349: ......
Page 350: ......