6. Description of Parameters
- 108 -
6
Ƶ
F4-11 = 3: Three-wire Control Mode 2
In this mode, DI3 is three-wire control command terminal. DI1 determines whether the
RUN command is enabled and DI2 determines running direction
.
The parameters are set as below:
Function Code
Parameter Name
Value
Function Description
F0-02
Command source selection
1
Terminal I/O control
F4-11
Terminal I/O control mode
3
Three-wire control mode 2
F4-00
DI1 function selection
1
Forward RUN (FWD)
F4-01
DI2 function selection
2
Reverse RUN (REV)
F4-01
DI2 function selection
3
Three wire control
SW3 is a normally-closed button and SW1 and SW2 are normally-open buttons.
Ɣ
SW3 must remain closed during start sequence and during normal run operation.
Ɣ
Motor stops immediately when SW3 opens.
Ɣ
Signals from SW1 and SW2 are valid only with SW3 closed.
Ɣ
On normal condition (SW3 closed), after you press down SW1, motor rotates in
forward direction with SW2 open. Motor rotates in reverse direction with SW2 closed.
Figure 6-9 Three-wire 2 sequence wiring diagram
DI1
Three-wire control
Run enabled
DI2
COM
Running direction
DI3
SW1
SW2
SW3
0/1
1
1
0/1
0
1
Running Command
Stop
Forward
Reverse
SW2
SW1
0
1
1
SW3
7KHWLPLQJGLDJUDPRIWKHWKUHHZLUHFRQWUROPRGHLVVKRZQLQWKHIROORZLQJ¿JXUH
Figure 6-10 Three-wire 2 sequence
Motor speed
Stop
SW2 off
SW2 on
SW1 (run
Enabled command)
Motor rotates in
forward direction
Motor rotates in
reverse direction
SW3 (three-wire
control command)
SW2 (forward/
reverse direction)
Summary of Contents for MD290 Series
Page 1: ......
Page 79: ...3 Electrical Installation 78 3 ...
Page 80: ...4 Operating Panel Keypad Display 4 1 Introduction 80 4 2 Inbuilt LED Operating Panel 80 ...
Page 92: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 92 5 2 Setup Flowchart 93 ...
Page 227: ...7 Interfaces and Communication 226 7 ...
Page 285: ...10 Troubleshooting 284 11 ...
Page 349: ......
Page 350: ......