6. Description of Parameters
- 191 -
6
Function Code
Parameter Name
Setting Range
Default
F5-09
Max. FMP output frequency
0.01 to 100.00 kHz
50.00 kHz
This function parameter sets maximum pulse output frequency when FM terminal is used for
pulse output.
Function Code
Parameter Name
Setting Range
Default
F5-10
$2]HURRIIVHWFRHI¿FLHQW
-100.0% to 100.0%
0.0%
F5-11
AO1 gain
-10.00 to 10.00
1.00
F5-12
$2]HURRIIVHWFRHI¿FLHQW
-100.0% to 100.0%
0.00%
F5-13
AO2 gain
-10.00 to 10.00
1.00
These four function parameters generally correct zero offset of analog output and output
DPSOLWXGHHUURU7KH\FDQDOVRGH¿QHUHTXLUHG$2FXUYH
=HURRIIVHWFRHI¿FLHQWRI$2DQG$2FRUUHVSRQGVWR9RUP$<RXFDQFDOFXODWH
WKHJDLQDQGWKH]HURRIIVHWFRHI¿FLHQWIURPWKHIROORZLQJIRUPXODV
K
=
(Y1
̢
Y2) x Xmax
(X1
̢
X2) x Ymax
b =
(X1 xY2
̢
X2 x Y1)
(X1
̢
X2) x Ymax
In the formulas:
Ɣ
"b" represents zero offset.
Ɣ
"k" represents gain.
Ɣ
"X" represents output frequency.
Ɣ
"Y" represents actual output of the AO.
Ɣ
" Xmax " represents max. output frequency (determined by F0-10).
Ɣ
"Ymax" represents max. output 10 V or 20 mA.
For example, AO is used for output of frequency reference. To implement output of 8 V (Y1) at 0
Hz (x1) and output of 4 V (Y2) at 40 Hz (X2) according to the formulas, you can obtain gain and
]HURRIIVHWFRHI¿FLHQWDVIROORZV
K =
(8
̢
4) x 50
(0
̢
40) x 10
=
̢
0.5
b =
(0 x 4 - 40 x 8)
(0 - 40) x 10
= 80%
Then you can set F5-11 to -0.5 and set F5-10 to 80%.
AO output signal type and corresponding max. value are as follows:
AO1 output signal
Corresponding Max. Output (Ymax)
Voltage
10 V
Current
20 mA
Summary of Contents for MD290 Series
Page 1: ......
Page 79: ...3 Electrical Installation 78 3 ...
Page 80: ...4 Operating Panel Keypad Display 4 1 Introduction 80 4 2 Inbuilt LED Operating Panel 80 ...
Page 92: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 92 5 2 Setup Flowchart 93 ...
Page 227: ...7 Interfaces and Communication 226 7 ...
Page 285: ...10 Troubleshooting 284 11 ...
Page 349: ......
Page 350: ......